PRODUCT IDENTIFICATION
According to UNE standard 23035/4:
- Manufacturer's name or brand
- Manufacturing date
- Denomination (class A or class B as applicable)
According to RIPCI 513/2017:
- Batch number
MINIMUM LUMINESCENCE VALUES AFTER SALT CHAMBER
All NMZ signage undergoes various internal and external light response tests that ensure compliance with the light intensity values outlined in UNE standard 23035.
CLASS A:
| Time | UNE 23035-4 (2003) Values CLASS A |
Values Sekureco CLASS A |
|---|---|---|
| Luminescence 10 minutes | 210 mcd/m2 | 225 mcd/m2 |
| Luminescence 60 minutes | 29 mcd/m2 | 30 mcd/m2 |
| Decay time: | 3,000 minutes | 3,100 minutes |
CLASS B:
| Time | UNE 23035-4 (2003) Values CLASS B |
Values Sekureco CLASS B |
|---|---|---|
| Luminescence 10 minutes | 40 mcd/m2 | 50 mcd/m2 |
| Luminescence 60 minutes | 5.6 mcd/m2 | 6.1 mcd/m2 |
| Decay time: | 800 minutes | 900 minutes |
CHARACTERISTICS
SUPPORT MATERIALS PVC
According to UNE standard 53127:
- White PVC 1mm for class A and transparent PVC 0.7mm and 0.5mm for class B
- White lacquered aluminum 0.6mm thick.
- Stability with Tª < 55º.
- Negligible water absorption (0.04 ± 0.01)%.
- Non-combustible.
- No appreciable lead and phosphorus content (less than 0.01%)
- Non-toxic.
PICTOGRAMS
According to standards:
- UNE EN ISO 7010
- UNE 23033/1
TEXTS
- According to UNE standard 23033/1
PHOTOLUMINESCENT PRODUCT
- Compound based on pigments.
- Unlimited photo-luminescent charge and discharge cycles
COLOR
Shades according to standard:
- UNE EN ISO 7010
- UNE 23033/1
- High adhesion and resistance ink.
- Allows great flexibility in the final product.
- Non-flammable. Non-toxic
FINAL THICKNESS
Class A
- PVC 1.2 mm (±10%).
- ALUMINUM 0.8 mm (±10%).
Class B
- PVC 0.8 mm (±10%).
- ALUMINUM 0.7 mm (±10%).
REFERENCE
- Printed on the sign
DIMENSIONS
- According to UNE standard 23033/1
COLOR PERCENTAGES
- According to UNE standard 23033-1
MAXIMUM VIEWING DISTANCE
- Printed on the sign.
To calculate the necessary dimensions of a sign, the following formula will be applied, up to a maximum distance of 50 m:
S≥ L2 /2000
“S” represents the surface area of the sign in square meters, and “L” the distance in meters from which the sign can be perceived.
MEASURES
CLASS A
- A00415-C...............210X300 (Luminescent PVC 1mm)
- FA00915-C...............210X300 (Luminescent Aluminum 0.5mm)
CLASS B
- B00115-C...............210X300 (Luminescent PVC 0.7mm)
NORMS
- UNE 23033/1:2019 (Extinction) - Fire safety. Signage
- UNE 23033/2:2019 (Installations) - Fire safety. Safety signage. Part 2: Signage and identification of fire protection installations.
- UNE 23034/1998 (Evacuation) - Fire safety. Safety Signage. Evacuation routes.
- UNE 23035-1/2003 - Fire safety. Photoluminescent signage-
- UNE 23035-4/2003 - NMZ signs periodically exceed radioactivity tests that guarantee the non-emission of the signaling element in compliance with UNE standard 23035-4.
- UNE 53127/2002 - Cellular plastics. Determination of the combustion characteristics of specimens in a horizontal position subjected to a small flame.
- UNE EN ISO 7010 : 2012 - Graphical symbols. Colors and safety signals. Registered safety signs (ISO 7010:2011) (Ratified by AENOR in September 2012.)
- RD 314/2006 (CTE - Technical Building Code)
- RIPCI 2017 (Extinction) - Regulation of Fire Protection Installations.
- NMZ signs are manufactured with a certified quality management system UNE-EN ISO 9001
STORAGE, CLEANING AND CONSERVATION
The working temperature should not exceed 45º C. Higher temperatures may deform the support material.
The optimal storage temperature will be between 15º C and 25º C; with a humidity of 10/50%.
Cleaning methods; avoid applying abrasive products. It is recommended to clean them with water and neutral detergents.
The technical building code – Basic document on fire safety requires that photoluminescent signage must comply with UNE standard 23035.
In order to maintain the functionality for which the signaling systems have been conceived, SEKURECO recommends keeping the signs free of dust, dirt, or any residue or object that prevents visibility and identification of the same.
For cleaning, it is advisable to use soapy solutions preferably, avoiding the use of solvents or abrasive products that may deteriorate the surface of the sign.
Photoluminescent signs should be positioned in such a way that they receive energy from a natural or artificial light source to ensure their proper functioning.
According to RD 513/2017 (TABLE III), luminescent signaling systems must undergo an annual inspection/review carried out by specialized personnel from the manufacturer, a maintenance company, or by the user or owner personnel of the installation.
Once the useful life period of the signs that make up the signaling system has elapsed, the inspection of these elements will be carried out following the indications collected in RD 513/2017 and UNE 23035-2
SIGN INSTALLATION
Check our blog to learn how to install a sign or poster: https://www.sekureco.eu/gb/blog/76_.html
THE RECOMMENDED INSTALLATION HEIGHT ranges between 2 and 2.50 meters, always maintaining a separation distance of 0.30 meters from the ceiling.
Photoluminescent signs should be positioned to receive energy from a natural or artificial light source to ensure their proper functioning.
The FIXING of the signaling element must be done on a firm surface free of dirt.
The sign can be secured using MECHANICAL ELEMENTS (screws, rivets, etc...) or ADHESIVES (mounting adhesive, glues, silicones…) carefully, avoiding soiling the visible surface or deforming it.
EVACUATION signage should be installed in such a way that from any point likely to be occupied in the premises, an evacuation can be initiated, so it is recommended to install directional signs on all routes, intersections, stairs, etc. that serve as a path.
Signage on DOORS will be placed above the lintel with the appropriate label (“EXIT”, “EMERGENCY EXIT”, “NO EXIT”, …).
Signage for FIRE protection, rescue, and/or assistance will be carried out on the same elements to be signaled whenever possible.
SOBRE SEKURECO
Sekureco es una empresa que surge en 2016 gracias a la pasión de varios técnicos especializados en prevención y seguridad laboral y ante la falta de empresas realmente especializadas en protección laboral en el mercado.
@CUSTOMER_NAME@
@AUTHOR_PROFILE@ @COMMENT_ISO_COUNTRY@ @VERIFY_PURCHASE@@COMMENT_TITLE@
@COMMENT_COMMENT@